Web Manager "Settings" Menu Options 163
Configuring IPDU Power Management
exists), the OnBoard generates an alarm. The type of alarm depends on
whether “Enable syslog” or “Enable buzzer” or both are checked.
Checking “Enable syslog” causes syslog messages to be sent to the
console if the maximum current is exceeded.
Checking “Enable buzzer” causes a buzzer to sound on the AlterPath PM
if the maximum current is exceeded.
Checking the “Enable Over Current Protection” checkbox brings up the table
like the one in the following screen example. The example shows entries for a
Master and a Slave Unit, with Alarm Threshold values already configured by
an administrative user.
Figure 6-12:Settings IPDU General Screen
Clicking the Edit button in the entry for an IPDU brings up the screen shown
in the following screen example.
Figure 6-13:Edit Alarm Threshold for IPDU Dialog
The appropriate value to enter in the “Alarm Threshold” field varies from one
AlterPath PM to the other. The value can be entered either as a number or as a
number with a decimal point, for example, 10 amps or 14.5 amps.